I. In the case of vector control 2 with encoder speed feedback or torque control, why did the inverter have too large running current or report E.oL1 error? 
A: Check the software setup:
A: (1) Check if the motor parameters are properly set;
A; (2) Check if the number of pulses per turn of the encoder Pd.21 is properly set;
A: (3) Check if the deceleration ratio between motor and encoder Pd.24 is properly set;
A: (4) If the above three parameters are properly set, change the value of Pd.22. If it is 0, change it to 1; while if it is 1, change it to 0.
Check the hardware connection:
A: (1) Check if the PG card matches the encoder;
A: (2) Check if the PG card and the encoder are properly connected, check if there is any loose connection or broken wire;
A: (3) Check if the connectors of the PG card and inverter control board are loose or dislocated;
A: (4) Check if the control lines for the V6−H−4T18.5G/22L and current sensor of above power class are loose or dislocated.


II. Why did the inverter have abnormal operation upon vector control 2 without encoder speed feedback?
A: (1) Check if there exists large difference between the power class of the motor and that of the inverter;
A: (2) Check if parameter auto-tuning has been performed under vector control 2. For details, refer to the setting process for parameter auto-tuning in Appendix B.
A: (3) Check if the control lines for the V6−H−4T18.5G/22L or current sensor of above power class are loose or dislocated.


III. Why did the inverter have abnormal operation upon vector control 2 without encoder speed feedback or vector control 2 with encoder speed feedback?
A: (1) Check if there exists large difference between the power class of the motor and the inverter;
A: (2) Check if parameter auto-tuning has been performed under vector control 2. For details, refer to the setting process for parameter auto-tuning in Appendix B.
A: (3) Check if the torque reference channel and speed limiting channel are properly set. For details, refer to setting process for torque control in Appendix B.
A: (4) Check if the control lines for the V6−H−4T18.5G/22L or current sensor of above power class are loose or dislocated.


IV. Why did the inverter have abnormal operation upon vector control 1?
A: (1) Check if parameter auto-tuning has been performed under vector control 1. For details, refer to the setting process for parameter auto-tuning in Appendix B.
A: (2) Check if the control lines for the V6−H−4T18.5G/22L or current sensor of above power class are loose or dislocated.
V. Why was the operating frequency of the inverter kept at 0Hz upon reverse operation?
A: (1) Check if the frequency is set as 0;
A: (2) Check if the inverter function code parameter P3.09 is set as 0. If not, change it to 0.


VI. The inverter had been connected with braking resistor featuring dynamic braking, why didn’t it work?
A: (1) Check if the braking resistor is connected between the main circuit terminals B1 and B2;
A: (2) Check if the inverter function code parameter PA.09 is set as 1. If not, change it to 1.


VII. Why was there large deviation on the correspondence relation between the analog input and the setting frequency?
A: (1) Check if the jumpers of analog input type and control board are properly set. For the analog voltage input, toggle the corresponding channel to the V end of the jumper; for the analog current input, toggle the corresponding channel to the I end of the jumper.
A: (2) Calibrate the analog input curve according to function codes P6.00 to P6.2. For details, refer to the description of P6 group in Chapter 6 Parameter Description.


VIII. Why was there large deviation on the correspondence relation between the analog output and the relevant function output?
A: (1) Check if the jumpers of analog output type and control board are properly set. For the analog voltage output, toggle the corresponding channel to the V end of the jumper; for the analog current output, toggle the corresponding channel to the I end of the jumper.
A: (2) Calibrate the analog output curve according to function codes P7.05 to P7.09. For details, refer to the description of P7 group in Chapter 6 Parameter Description.


IX. Why did the inverter report E.AIF analog input abnormal error?
A: (1) Check if the jumpers of analog input type and control board are properly set. For the analog voltage input, toggle the corresponding channel to the V end of the jumper; for the analog current input, toggle the corresponding channel to the I end of the jumper.
A: (2) Check if the analog input exceeds 11V;
A: (3) When using the +10V power supply of the inverter control board, check if the voltage of +10V is lower than 9V or higher than 11V. If yes, check if the resistance value between the +10V and the GND is less than 1KΩ after the inverter is powered off completely.


X. Why did the inverter report E.P10 abnormal error?
A: Check if the voltage of +10V on the inverter control board is lower than 9V or higher than 11V. If yes, check if the resistance value between the +10V and the GND is less than 1KΩ after the inverter is powered off completely.
XI. Why did the PLC and inverter have abnormal 485-based communication?
A: (1) Check if the data format, address and baud rate of the inverter are consistent with that of the PLC;
A: (2) Check if the PLC address needs add 1 operation;
A: (3) Check if the PLC adopts Modbus RTU format;
A: (4) Check if the register address of the PLC is converted to hexadecimal format;
(5) Check if the 485 wires are properly connected.


XII. Why did there exist abnormality upon parameter copying?
A: (1) The parameters for V5 inverter and V6 inverter cannot be copied between each other;
A: (2) The copy operation can be performed only when the upload and download function codes of the inverter d1.09 (operation panel copy identification code) are consistent;
A: (3) The copy function can be completed only when the inverter is completely powered down and then powered up after the download of the parameters for copy is completed.


XIII. Why did the keyboard will have “8.8.8.8” display or have no display sometimes?
A: (1) Check if the connectors are properly connected when the operation panel is directly connected to the inverter control board;
A: (2) Check if the connection wire signals are in one to one correspondence when the keyboard is connected to the operation panel and inverter control board through customized extension wires;
A: (3) Check if the network cable connectors of the operation panel and inverter control board are properly connected when standard network cable is used to connect the operation panel and inverter control board.


XIV. Why couldn’t display or modify the function codes of the operation panel?
A: (1) When the modification could not be performed, check if P0.01 is set as 1. If not, change it to 0.
A: (2) When the modification could not be performed, check if the function code has been set as modification disabled;
A: (3) When the modification could not be performed upon running, check if the function code could not modification upon running;
A: (4) When display is not available, check if the inverter function code has been encrypted;
A: (5) When display is not available, check if the inverter operation panel has been locked;


XV. How could the motor keep the locking force in static status?
A: (1) Adopt zero-speed running mode upon vector control 2 with encoder speed feedback;
A: (2) Enable the inverter zero-servo function.


XVI. How to change the direction that the inverter drives the motor to rotate?
A: (1) In the case of operation panel control, the direction is determined by P0.07. However, the FWD/REV key on the operation panel can real time change the direction.
A: (2) In the case of operation panel control, the direction is determined by P0.07. However, the UP/DN key on the operation panel (or the FWD/REV knob of the shuttle operation panel) can real time change the direction.
A: (3) In the case of operation panel control, the positive/negative frequency value resulting from the final frequency calculation for composite control can also change the direction in real time.
A: (4) In the case of terminal control, check if the forward/reverse terminal is in one to one correspondence with that of the control equipment (e.g. PLC).


XVII. Why did the fans of inverters of certain power classes will rotate upon power up, while others could not?
A: The fans of the 15KW inverters and inverters of lower power class are under no control, and they will run when powered up. The operation of the fans of 18.5KW inverters and inverters of higher power class is controlled by the heatsink temperature. When the inverter is powered up under low temperature condition, the fans will not run.


XVIII. What will happen if the CN1 busbar of the control board is loose or damaged?
A: If the CN1 busbar of the control board is loose or damaged, the inverter cannot run or will report several errors. For instance, the inverter may display “-LU- "or “relay/contactor could not pull on “, or report such errors as E.oc1, E.FAL, E.oH1, E.oH2, E.Cur and E.dL3.

联系我们

Tel: +86-0755-26580810
Fax: +86-0755-26580821
E-Mail: lhht@v-t.net.cn
Add: 6F, XinFeng Buliding B, YangGuang, XiLi Town, NanShan District, ShenZhen, China.
Web: http://www.v-t.net.cn
Marketing: +86-0755-26580820
Service: +86-0755-26580830

最新动态 / 更多>>
2018 . 05 . 15
点击次数: 0
OnMay 8-11, 2018, the 13th World Elevator & Escalator Expo kicked off in the International Convention and Exhibition Center (Shanghai), with over 1,300 elite enterprises in elevator industry from ...
2017 . 10 . 28
点击次数: 361
On August 9th to 12th 2017, The 12th India international trade exhibition was ceremoniously held in Mumbai, India. V&T brought innovative technology products and a technological feast at home and ...
2015 . 03 . 24
点击次数: 244
January 11, 2011, China’s electrical industry, will be a very significant day. Electrical network sponsored by the HC, China Electrical Equipment Industrial Association and the China Electrotechnical ...
2015 . 03 . 24
点击次数: 208
11th China International Petroleum Petrochemical Equipment Exhibition will be held March 22, 2011 to 24 in Beijing International Exhibition Center (New Hall); Shenzhen V&T Technology Co., Ltd. wil...
2015 . 03 . 24
点击次数: 152
We held a "how to improve service" training in Shenzhen, NanYong Hotel, 10 April 2011 , more than 100 delegates, cooperative partners spoke enthusiastically, especially the Wang general...
2015 . 03 . 24
点击次数: 143
May 26, 2011 -29 days, Shenzhen V&T Technology Co., Ltd. participated the "China International Ceramics Industry Exhibition 2011 " in GuangZhou, YongZhou Hotel, the exhibition organized ...
WeChat
Mobile
Add: Kenuo Building, Kenuo Industrial Park, No. 7 Road, Tongguan Avenue, Guangming District, Shenzhen City, China.
24-hour hotline: 86-400 080 1199
 
传真:+86 0755-2788 8009
 
Copyright ©2005 - 2018     Shenzhen V&T Technologies Co., Ltd.