◆ First step, must disconnected from the load. If the motor can be disconnected from the load, it can select rotation auto-tuning (P9.15=2), or it can select static auto-tuning only.◆ If the inverter power does not match the motor power, select static auto-tuning. after the tuning, manually change the no load current P9.05 to about 40% of the motor rated current P9.04◆ Setting P0.01=5,recover parameter to factory setting◆ Setting motor basic frequency P0.15 according to motor nameplate◆ Setting motor rated voltage P0.12 according to motor nameplate◆ Setting motor pole P9.01 according to motor ...
发布时间: 2015 - 03 - 24
浏览次数:19
E5 V5 V6  Hardware Digital input terminal X1~X4 X1~X7/DI X1~X7/DI Support DI input NO YES YES Digital putput terminal 1(Y1) 2(Y1 and Y2/DO) 2(Y1 and Y2/DO) Relay 1(RA-RB-RC) 1(RA-RB-RC) 1(RA-RB-RC) Analog 2(AI1 and AI2) 3(AI1、AI2、AI3) 3(AI1、AI2、AI3) Analog input support +10V~-10V NO YES(AI3) YES(AI3) Analog output 2 2 2 Support DO output NO YES(Y2/DO) YES(Y2/DO) Support dual 485 NO (*) YES YES Support operation panel 485 YES YES YES Support extension card NO(*) YES YES Support built in braking unit 15kw and  below power built in as standard. 15kw and below power built in as stan...